Mitsubishi Electric 800 Series Instruction Manual page 183

Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

5.4.16
Inverter parts life display
The degree of deterioration of the control circuit capacitor, main circuit capacitor, cooling fan, inrush current limit circuit, and
relay contacts of terminals A, B, and C can be diagnosed on the monitor.
When a part approaches the end of its life, an alarm can be output by self diagnosis to prevent a fault.
(Note that the life diagnosis of this function should be used as a guideline only, because with the exception of the main circuit
capacitor, the life values are theoretical calculations.)
Pr.
255
Life alarm status display
E700
256
Inrush current limit circuit life
display
*2
E701
257
Control circuit capacitor life display
E702
258
Main circuit capacitor life display
*2
E703
259
Main circuit capacitor life measuring 0
*2
E704
506
Display estimated main circuit
*2
capacitor residual life
E705
507
Display/reset ABC1 relay contact life 100%
E706
508
Display/reset ABC2 relay contact life 100%
E707
*1
The setting range (read-only) differs depending on the inverter model (standard model or separate converter type).
*2
The setting is available only for standard models.
182
5. PARAMETERS
5.4 (E) Environment setting parameters
Name
Initial value
0
100%
100%
100%
100%
Setting range
*1
Displays whether or not the parts of the control
(0 to 255)
circuit capacitor, main circuit capacitor, cooling fan,
and inrush current limit circuit have reached the life
alarm output level. Read-only.
(0 to 100%)
Displays the deterioration degree of the inrush
current limit circuit. Read-only.
(0 to 100%)
Displays the deterioration degree of the control
circuit capacitor. Read-only.
(0 to 100%)
Displays the deterioration degree of the main
circuit capacitor. Read-only.
The value measured by Pr.259 is displayed.
0, 1(2, 3, 8, 9)
Setting "1" and turning the power supply OFF
starts the measurement of the main circuit
capacitor life.
If the setting value of Pr.259 becomes "3" after
turning the power supply ON again, it means that
the measurement is completed. The deterioration
degree is read to Pr.258.
11(12, 13, 18,
When "11" is set, turning OFF the power supply
19)
starts the measurement of the main circuit
capacitor life.
If the setting value of Pr.259 becomes "13" after
turning the power supply ON again, it means that
the measurement is completed. The degree of
deterioration is read to Pr.258.
(0 to 100%)
Displays the estimated residual life of the main
circuit capacitor. Read-only.
0 to 100%
Displays the degree of deterioration of the relay
contacts of terminals A1, B1, and C1.
0 to 100%
Displays the degree of deterioration of the relay
contacts of terminals A2, B2, and C2.
Description