5.10.2
Offline auto tuning
Magnetic flux
Magnetic flux
Magnetic flux
The offline auto tuning enables the optimal operation of an motor.
• Under Advanced magnetic flux vector control, automatic measurement of motor constants (offline auto tuning) enables
optimal operation of motors even when motor constants vary, when a motor of another company is used, or when the wiring
distance is long.
For the offline auto tuning for a PM motor, refer to
Pr.
Name
684
Tuning data unit
C000
switchover
71
Applied motor
C100
80
Motor capacity
C101
81
Number of motor poles
C102
9
Electronic thermal O/L
C103
relay
83
Rated motor voltage
C104
84
Rated motor frequency
C105
707
Motor inertia (integer)
C107
724
Motor inertia (exponent) 9999
C108
96
Auto tuning setting/
C110
status
90
Motor constant (R1)
C120
91
Motor constant (R2)
C121
92
Motor constant (L1)/d-
C122
axis inductance (Ld)
93
Motor constant (L2)/q-
C123
axis inductance (Lq)
94
Motor constant (X)
C124
82
Motor excitation current 9999
C125
859
Torque current/Rated
C126
PM motor current
298
Frequency search gain
A711
450
Second applied motor
C200
page
363.
Initial value
Setting range
0
0
1
0
0 to 6, 13 to 16, 8090, 8093,
8094, 9090, 9093, 9094
9999
*1
0.4 to 55 kW
*2
0 to 3600 kW
9999
9999
2, 4, 6, 8, 10, 12
9999
Inverter
*1
0 to 500 A
rated
*2
0 to 3600 A
current
575 V
0 to 1000 V
9999
10 to 400 Hz
9999
9999
10 to 999, 9999
0 to 7, 9999
0
0
1
11
101
9999
*1 *3
0 to 50 Ω, 9999
0 to 400 mΩ, 9999
9999
*1 *3
0 to 50 Ω, 9999
0 to 400 mΩ, 9999
9999
0 to 6000 mH, 9999
0 to 400 mH, 9999
9999
0 to 6000 mH, 9999
0 to 400 mH, 9999
9999
*3
0 to 100%, 9999
*1 *3
0 to 500 A, 9999
0 to 3600 A, 9999
9999
*1*3
0 to 500 A, 9999
0 to 3600 A, 9999
9999
0 to 32767
9999
9999
0, 1, 3 to 6, 13 to 16, 8090, 8093,
8094, 9090, 9093, 9094
9999
Internal data converted value
The value is indicated with "A, Ω, mH or %".
By selecting a motor, the thermal characteristic
and motor constant of each motor are set.
Set the applied motor capacity.
V/F control
Set the number of motor poles.
V/F control
Set the rated motor current.
Set the rated motor voltage (V).
Set the rated motor frequency (Hz).
Use the value set in Pr.3 Base frequency.
Set the motor inertia.
9999: Uses the constant value of standard motor.
No offline auto tuning
Performs offline auto tuning without rotating the
motor
Performs offline auto tuning without rotating the
motor (V/F control)
(Refer to
page
363)
Performs offline auto tuning by rotating the motor
Tuning data
(The value measured by offline auto tuning is
*2 *3
automatically set.)
9999: Uses the constant value of standard motor.
*2 *3
*1 *3
*2 *3
*1 *3
*2 *3
*2 *3
*2*3
The offline auto tuning automatically sets the gain
required for the frequency search.
Uses the constant value of standard motor.
Set this parameter when using the second motor.
(the same specifications as Pr.71).
The function is disabled.
5.10 (C) Motor constant parameters
Description
5. PARAMETERS
3
4
5
5
5
6
7
8
9
10
353