NOTE
• When both the forward rotation switch (STF) and the reverse rotation switch (STR) are ON, the motor cannot be started.
If both are turned ON while the inverter is running, the inverter decelerates to a stop.
• Pr.178 STF terminal function selection must be set to "60" (or Pr.179 STR terminal function selection must be set to
"61"). (All are initial values.)
• Setting Pr.79 Operation mode selection="3" also enables multi-speed operation.
• If stopped using
on the operation panel during the External operation, the inverter enters the PU stop status. ([PS]
appears on the operation panel.) To reset the PU stop status, turn OFF the start switch (STF or STR), and then press
. (Refer to
page
164)
Parameters referred to
Pr.4 to Pr.6 (multi-speed setting)
Pr.7 Acceleration time, Pr.8 Deceleration time
Pr.178 STF terminal function selection
Pr.179 STR terminal function selection
Pr.79 Operation mode selection
page 226
page 190
page 343
page 343
page 204
4. BASIC OPERATION
4.3 Basic operation procedure (External operation)
3
4
5
4
5
6
7
8
9
10