General flowchart
CAUTION
• Always set the communication check time interval before starting operation to prevent hazardous conditions.
• Data communication is not started automatically but is made only once when the computer provides a communication request. If
communication is disabled during operation due to signal cable breakage etc., the inverter cannot be stopped. When the communication
check time interval has elapsed, the inverter will trip (E.PUE, E.SER). The inverter can be coasted to a stop by switching ON the RES
signals or by switching the power OFF.
• If communication is broken due to signal cable breakage, computer fault etc., the inverter does not detect such a fault. This should be
fully noted.
494
5. PARAMETERS
5.12 (N) Operation via communication and its settings
Port open
Communication setting
Time out setting
Send data processing
○Data setting
○Sum code calculation
○Data transmission
Receive data waiting
Receive data processing
○Data retrieval
○Screen display