5.9.2
Analog input terminal (terminal 1, 4) function assignment
The analog input terminal 1 and terminal 4 functions are set and changeable with parameters.
Pr.
868
Terminal 1 function assignment
T010
858
Terminal 4 function assignment
T040
• Concerning terminal 1 and terminal 4 used for analog input, the frequency (speed) command, stall prevention operation
level input, and other similar commands are usable. The functions available are different depending on Pr.868 Terminal
1 function assignment, Pr.858 Terminal 4 function assignment as shown in the table below.
Setting
Terminal 1 function (Pr.868)
value
0
Frequency setting auxiliary
(initial value)
4
Stall prevention operation level
input
9999
―: No function
*1
Invalid when Pr.868 = "4"
NOTE
• When Pr.868 = "4" (stall prevention), the terminal 4 function is enabled whether the AU terminal is turned ON/OFF.
322
5. PARAMETERS
5.9 (T) Multi-Function Input Terminal Parameters
Name
Initial value
0
0
Terminal 4 function (Pr.858)
Frequency command (AU signal-
ON)
Stall prevention operation level
*1
input
Setting range
0, 4, 9999
Select the terminal 1 function (Refer to the
table below.)
0, 4, 9999
Select the terminal 4 function (Refer to the
table below.)