 To run with an analog input voltage
• Concerning the frequency setting signal, input 0 to 5 VDC (or 0 to 10 VDC) to terminals 2 and 5. The 5 V (10 V) input is
the maximum output frequency.
• The power supply 5 V (10 V) can be input by either using the internal power supply or preparing an external power supply.
The internal power source is 5 VDC output between terminals 10 and 5, and 10 VDC output between terminals 10E and 5.
Terminal
Inverter internal
power source
voltage
10
5 VDC
10E
10 VDC
• To supply the 10 VDC input to terminal 2, set "0, 2, 4, 10, 12, or 14" in Pr.73. (The initial value is 0 to 5 V.)
• Setting "1 (0 to 5 VDC)" or "2 (0 to 10 VDC)" in Pr.267 and turning the voltage/current input switches OFF sets the terminal
4 to the voltage input specification. Turning ON the AU signal activates terminal 4 input.
Forward
rotation
0 to 5 VDC
Frequency
setting
Connection diagram using
terminal 2 (0 to 5 VDC)
NOTE
• The wiring length of the terminal 10, 2, 5 should be 30 m at maximum.
320
5. PARAMETERS
5.9 (T) Multi-Function Input Terminal Parameters
Frequency setting
resolution
0.030 Hz/60 Hz
0.015 Hz/60 Hz
Inverter
STF
Forward
Voltage/current
SD
rotation
input switch
10
2
Frequency
setting
5
2
4
using terminal 2 (0 to 10 VDC)
Pr.73 (terminal 2
input voltage)
0 to 5 VDC input
0 to 10 VDC input
Inverter
STF
Voltage/current
input switch
SD
0 to 10 VDC
10E
2
5
2
4
Connection diagram
Forward
Inverter
STF
rotation
AU
Terminal 4
input selection
SD
0 to 5 VDC
10
Frequency
4
setting
5
Connection diagram
using terminal 4 (0 to 5 VDC)
Voltage/current
input switch
2
4