FusionModule500 Smart Mini Data Center
User Manual (ECC800e)
Before removing a T/H sensor, remember the DIP switch setting on it. When you install a new
T/H sensor, you need to set the same DIP switch setting for the new one.
Step 4 Install a new T/H sensor on the base.
Step 5 Reconnect cables to the new T/H sensor.
----End
4.5.3.13 Replacing a Smoke Sensor
Prerequisites
Context
The smoke sensor needs to be installed in the Converged Cabinet.
Procedure
Step 1 Remove the smoke sensor from the base by pressing the spring of the base and sliding out the
smoke sensor, as shown in
Figure 4-24 Removing a smoke sensor
Step 2 Remove the cables from the smoke sensor and apply insulation measures such as wrapping
the cables with insulation tape to avoid hazards.
Issue 07 (2019-12-20)
Recommended tools and materials: Phillips screwdriver, insulation tape, step ladder (2
m)
A smoke sensor needs to be replaced.
A spare smoke sensor of the same model is available and functional.
Figure
Copyright © Huawei Technologies Co., Ltd.
4-24.
4 Maintenance
197