FusionModule500 Smart Mini Data Center
User Manual (ECC800e)
Figure 4-14 Removing a battery current sensor
Step 5 Unplug the battery current sensor, cut off the cable ties, and remove the faulty battery current
sensor, as shown by (2) in
Step 6 Install the new battery current sensor by referring to the preceding method and connect cables.
Keep the Up arrow on the current sensor of the positive battery copper bar downwards, and
keep the Up arrow on the current sensor of the negative battery copper bar upwards.
Step 7 Reinstall the removed components, and close the corresponding cabinet door.
----End

4.5.3 Replacing Monitoring System Components

After replacing a component of the monitoring system, set parameters for the new component
to ensure normal communication. For details, see
Issue 07 (2019-12-20)
After removing cables, insulate the cable terminals.
When removing cables, label the cables with corresponding terminal ports for later
connection.
For devices connected to the FE port on the ECC800e, set parameters by referring to
3.2.8 (Optional) Commissioning CIMs and BIMs
one.