Procedure
Step 1 Set functions of the infrared remote control module on the WebUI.
1.
2.
3.
4.
5.
6.
7.
8.
Step 2 (Optional) Set functions on the infrared remote control module.
1.
2.
Issue 07 (2019-12-20)
You have obtained the IP address of the ECC800e as well as the user name and password
used for WebUI login.
A PC with an IP address in the same network segment as that of the ECC800e is
prepared, and the PC has connected to port WAN on the ECC800e.
The infrared remote control module supports self-learning and can remotely control the
startup of the civil smart cooling product.
The infrared remote control module can be in infrared learning state and control code
sending state. After power-on, the device is in normal operating mode by default.
Log in to the ECC800e WebUI as an administrator.
Choose System Settings > Linkage Control, set Enable linkage control function to
Yes, and click Submit.
Choose Monitoring > System > Infrared Remote Control Module.
On the Controls tab page, choose Learning the startup instruction, and click Submit.
Direct the smart cooling product remote control to the infrared receiving place on the
infrared remote control module, and then press the power button once.
If you do not press the button within 20s, the smart cooling product remote control will exit the learning
mode due to a timeout. You can click Learning the startup instruction on the ECC800e WebUI and
start the learning mode again.
On the Controls tab page, choose Exiting the learning mode, and click Submit.
On the Controls tab page, choose Air conditioner startup, and click Submit. On the
displayed Re-Authentication window, enter password in the Login Password box, and
click Submit.
Check whether the smart cooling product starts. If it starts, the control function works; if
it cannot start, rectify the fault and perform the preceding steps again.
After you perform Learning the startup instruction on the WebUI, check the indicator status. If
the indicator on the infrared remote control module blinks yellow, it indicates that the infrared
remote control module enters the infrared learning state. If the green indicator blinks, it indicates
learning success of the key code. If the indicator is steady yellow, it indicates learning failure and
you need to rectify the faults and perform Learning the startup instruction again.
After you perform Air conditioner startup, check whether the smart cooling product starts. If it
starts, the control function works; if it cannot start, rectify the fault and perform the preceding steps
again.
After the device power-on, if the yellow indicator is steady on, it indicates that the
device has never learnt the infrared coding successfully. If the green indicator blinks, it
indicates that the device has learnt the infrared coding successfully. And the infrared
remote control module enters normal operating mode by default.
Press the SW button on the infrared remote control module for more than 3s. Then the
indicator blinks yellow and the infrared remote control module enters learning operating
mode.