FusionModule500 Smart Mini Data Center
User Manual (ECC800e)
Figure 2-77 Connecting the mains power cable
----End
2.3.2.4 (Optional) Connecting an rPDU Power Cable
Procedure
Step 1 Connect the power cable for the rPDU in the network cabinet.
1.
2.
3.
Issue 07 (2019-12-20)
Connect the cord end terminal of the power cable for the rPDU in the network cabinet to
the QF3 circuit breaker on the PDU5000 in the Converged Cabinet.
You can connect to circuit breakers QF3 to QF7 of the PDU5000 based on the actual situation.
If the Converged Cabinet uses a horizontal half-sized rPDU, you can connect to circuit breakers QF3
to QF6 of the PDU5000.
If the Converged Cabinet uses a vertical full-sized rPDU, you can connect to circuit breakers QF4 to
QF7 of the PDU5000.
Remove the front panel of the rPDU.
Connect the other end of the power cable for the rPDU in the network cabinet to the
rPDU terminal base.
Copyright © Huawei Technologies Co., Ltd.
2 Installation
79