Specifications - Huawei FusionModule500 User Manual

Smart mini data center
Hide thumbs Also See for FusionModule500:
Table of Contents

Advertisement

FusionModule500 Smart Mini Data Center
User Manual (ECC800e)
Check Item
Operating humidity
Physical environment of the
equipment room
Altitude
Equipment room height
Equipment room area
Equipment room
maintenance clearance
Load bearing capacity of the
equipment room
Issue 07 (2019-12-20)

Specifications

module, the room
temperature should be in
the range of 18° C to
27° C.
5–95% RH
The interior is clean and
tidy, free from dust and
conductive pollution.
0–4000 m (The power is
derated as described in
IEC62040-3 when the
altitude exceeds 1000 m.)
Equipment room height ≥
2.3 m
In the scenario with a 42
U cabinet, the equipment
room area is greater than
or equal to 3.9 m
In the scenario with a 24
U cabinet, the equipment
room area is greater than
or equal to 3.6 m
In the multi-cabinet
scenario, the equipment
room area is greater than
or equal to 10.15 m
At least 900 mm, 600 mm,
and 900 mm maintenance
clearance should be reserved
at the front door, rear, and
side of the cabinet,
respectively. The cabinet
can be installed against the
wall.
NOTE
In the scenario with a 24 U
cabinet, reserve at least
900 mm clearance at the
cabinet rear door for
maintenance.
In the scenario with four
cabinets, reserve at least
1200 mm clearance at the
cabinet front door for
maintenance.
Single cabinet scenario
Copyright © Huawei Technologies Co., Ltd.
2
.
2
.
2
.
Weight of the 24 U
cabinet ≤ 282 kg/m
2
2 Installation
Check Result
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed