2.3.3.3 (Optional) Connecting a Monitoring Cable to the T/H Sensor

Prerequisites
The T/H sensor is installed.
Procedure
Step 1 Connect the non-RJ45 (6-pin) end of the cable delivered with the device to the T/H sensor
terminal.
Step 2 Connect the T/H sensor monitoring cable.
Table 2-10 Connected ports
Scenario
Number of cabinets ≤ 2
Number of cabinets > 2
Issue 07 (2019-12-20)
The following figure uses the standalone AI/DI module as an example to describe the cabling route.
Copyright © Huawei Technologies Co., Ltd.
Device
status sensor
Network cabinet door status
sensor
Battery cabinet 1 door status
sensor
Battery cabinet 2 door status
sensor
Devices
Converged cabinet T/H
sensor
Network cabinet T/H sensor
Converged cabinet T/H
sensor
Network cabinet T/H sensor
2 Installation
Ports
ECC800e
AI/DI_1 port on the
standalone AI/DI module
AI/DI_2 port on the
standalone AI/DI module
AI/DI_3 port on the
standalone AI/DI module
Ports
COM2/12 V port on the
ECC800e
COM3/12 V port on the
ECC800e
COM2/12 V port on the
ECC800e
COM_OUT port on the
standalone AI/DI module
92