FusionModule500 Smart Mini Data Center
User Manual (ECC800e)
Figure 3-2 CIM
(1) Networking switch
Step 2 Hold down the networking switch on the BIM for 2 seconds. When the RUN/ALM indicator
turns from steady red to blinking green at super short intervals, and finally to blinking green at
long intervals, the BIM connects to the CIM network.
Figure 3-3 BIM
(1) RUN/ALM indicator
Step 3 Perform networking operations on the next BIM only after networking for the previous BIM
is successful. Repeat
Step 4 Press the CIM networking switch for 2 seconds. When the RF_Z indicator on the CIM turns
from blinking green at super short intervals to blinking green at long intervals, the networking
is complete.
Issue 07 (2019-12-20)
It is recommended that BIMs be networked from the positive battery string terminal according to the
battery cable connection sequence.
Batteries are numbered depending on the sequence of connecting BIMs to the CIM.
Step 2
Copyright © Huawei Technologies Co., Ltd.
(2) ALM indicator
(2) Networking switch
to add remaining BIMs to the CIM network.
3 Commissioning Guide
(3) RF_Z indicator
114