Section 6
Wide area measurement system
IEC140000119 V2 EN-US
Figure 35: Multiple instances of PHASORREPORT blocks
Figure
36
visible in the bottom of each function block. For each instance, there are three separate
ANALOGREPORT blocks capable of reporting up to 24 Analog signals (8 Analog signals in each
ANALOGREPORT block). These can include for example transfer of active and reactive power or
reporting the milliampere input signals to the PDC clients as defined in IEEE IEC/IEEE
60255-118 (C37.118) data frame format.
IEC140000120 V2 EN-US
Figure 36: Multiple instances of ANALOGREPORT blocks
Figure
37
visible in the bottom of each function block. For each instance, there are three separate
BINARYREPORT blocks capable of reporting up to 24 Binary signals (8 Binary signals in each
BINARYREPORT block). These binary signals can be for example dis-connector or breaker
position indications or internal/external protection alarm signals.
98
shows both instances of ANALOGREPORT function blocks. The instance number is
shows both instances of BINARYREPORT function blocks. The instance number is