1MRK 511 401-UEN Rev. K
the post-fault period and lasts longer than the proceeding recording a new complete
recording will be started.
Disturbance report function can handle a maximum of 3 simultaneous disturbance recordings.
18.6.4.2
Binary input signals
Up to 352 binary signals can be selected among internal logical and binary input signals. The
configuration tool is used to configure the signals.
For each of the 352 signals, it is also possible to select if the signal is to be used as a trigger
for the start of the Disturbance report and if the trigger should be activated on positive (1) or
negative (0) slope.
OperationN : Disturbance report may trig for binary input N ( On ) or not ( Off ).
TrigLevelN : Trig on positive ( Trig on 1 ) or negative ( Trig on 0 ) slope for binary input N.
Func103N : Function type number (0-255) for binary input N according to IEC-60870-5-103, that
is, 128: Distance protection, 160: overcurrent protection, 176: transformer differential
protection and 192: line differential protection.
Info103N : Information number (0-255) for binary input N according to IEC-60870-5-103, that is,
69-71: Trip L1-L3, 78-83: Zone 1-6.
See also description in the chapter IEC 60870-5-103.
18.6.4.3
Analog input signals
Up to 40 analog signals can be selected among internal analog and analog input signals.
PCM600 is used to configure the signals.
The analog trigger of Disturbance report is not affected if analog input M is to be included in
the disturbance recording or not (
If
OperationM = Off , no waveform (samples) will be recorded and reported in graph. However,
Trip value, pre-fault and fault value will be recorded and reported. The input channel can still be
used to trig the disturbance recorder.
OperationM = On , waveform (samples) will also be recorded and reported in graph.
If
NomValueM : Nominal value for input M.
OverTrigOpM , UnderTrigOpM : Over or Under trig operation, Disturbance report may trig for
high/low level of analog input M (
OverTrigLeM , UnderTrigLeM : Over or under trig level, Trig high/low level relative nominal value
for analog input M in percent of nominal value.
18.6.4.4
Sub-function parameters
All functions are in operation as long as Disturbance report is in operation.
Bay control REC670
Application manual
For retrieving remote data from LDCM module, the Disturbance report function
should be connected to a 8 ms SMAI function block if this is the only intended
use for the remote data.
OperationM = On / Off ).
On ) or not ( Off ).
© Copyright 2017 Hitachi Power Grids. All rights reserved
Section 18
Monitoring
M12179-90 v9
M12179-92 v6
M12179-389 v3