1MRK 511 401-UEN Rev. K
the user wants to generate logical commands (for selector switches or voltage controllers) by
inputting an integer number. ITBGAPC function has a logical node mapping in IEC 61850.
The Integer to Boolean 16 conversion with logic node representation function (ITBGAPC) will
transfer an integer with a value between 0 to 65535 communicated via IEC 61850 and
connected to the ITBGAPC function block to a combination of activated outputs OUTx where
1≤x≤16.
The values of the different OUTx are according to the Table 67.
If the BLOCK input is activated, it freezes the logical outputs at the last value.
Table 67:
Name of OUTx
OUT1
OUT2
OUT3
OUT4
OUT5
OUT6
OUT7
OUT8
OUT9
OUT10
OUT11
OUT12
OUT13
OUT14
OUT15
OUT16
The sum of the numbers in column "Value when activated" when all OUTx (1≤x≤16) are active
equals 65535. This is the highest integer that can be converted by the ITBGAPC function block.
17.12
Elapsed time integrator with limit transgression and
overflow supervision TEIGAPC
17.12.1
Identification
Function Description
Elapsed time integrator
17.12.2
Application
The function TEIGAPC is used for user-defined logics and it can also be used for different
purposes internally in the IED. An application example is the integration of elapsed time during
the measurement of neutral point voltage or neutral current at earth-fault conditions.
Bay control REC670
Application manual
Output signals
Type
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
IEC 61850
identificatio
n
TEIGAPC
© Copyright 2017 Hitachi Power Grids. All rights reserved
Description
Value when
activated
Output 1
1
Output 2
2
Output 3
4
Output 4
8
Output 5
16
Output 6
32
Output 7
64
Output 8
128
Output 9
256
Output 10
512
Output 11
1024
Output 12
2048
Output 13
4096
Output 14
8192
Output 15
16384
Output 16
32768
IEC 60617
ANSI/IEEE C37.2 device
identificatio
number
n
-
-
Section 17
Logic
Value when
deactivated
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
GUID-1913E066-37D1-4689-9178-5B3C8B029815 v3
GUID-B4B47167-C8DE-4496-AEF1-5F0FD1768A87 v2
465