ABB Relion 670 Series Applications Manual page 187

Bay control
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 511 401-UEN Rev. K
Table 26: Setting summary for FunctionMode, StartMode, RetripMode and BuTripMode
No.
StartMode
FunctionMode = Current
1
LatchedStart
2
LatchedStart
3
LatchedStart
4
FollowStart
5
FollowStart
6
FollowStart
7
FollowStart&
Mode
8
FollowStart&
Mode
9
FollowStart&
Mode
*) Set level depends on selected BuTripMode, that is, set level can be either IPh> or IN> or both.
No.
StartMode
FunctionMode = CB Pos
10
LatchedStart
11
LatchedStart
Table continues on next page
Bay control REC670
Application manual
RetripMode
t1 and t2 initiated
with
Off
external START
UseFunction
external START
Mode
Always
external START
Off
external START
UseFunction
external START
Mode
Always
external START
Off
external START
and current
above set level
UseFunction
external START
Mode
and current
above set level
Always
external START
and current
above set level
RetripMode
t1 and t2 initiated
with
Off
external START
UseFunction
external START
Mode
© Copyright 2017 Hitachi Power Grids. All rights reserved
When t1 has
When t2 or t2MPh
elapsed, TRRET will
has elapsed, TRBU
will be given if
never be given
current is above
set level *)
be given if current
current is above
is above set level
set level *)
of IPh>
always be given
current is above
set level *)
never be given
current is above
set level *)
be given if current
current is above
is above set level
set level *)
of IPh>
be given if external
current is above
START is present
set level *)
never be given
current is above
set level *) and
external START
present
be given if current
current is above
is above set level
set level *) and
of IPh> and
external START
external START is
present
present
be given if external
current is above
START is present
set level *) and
external START
present
When t1 has
When t2 or t2MPh
elapsed, TRRET will
has elapsed, TRBU
will be given if
never be given
CBCLDLx input has
logical value one
be given if
CBCLDLx input has
CBCLDLx input has
logical value one
logical value one
Section 8
Current protection
GUID-845257FF-2774-472A-B982-E9DDD8966988 v1
t1 and t2 and t2MPh
will be stopped
(reset) if
t1 and (t2 or
t2MPh) and 150ms
expires and
current is below
set level *)
t1 and (t2 or
t2MPh) and 150ms
expires and
current is below
set level *)
t1 and (t2 or
t2MPh) and 150ms
expires and
current is below
set level *)
external START
disappears
external START
disappears
external START
disappears
current is below
set level *) or
external START
disappears
current is below
set level *) or
external START
disappears
current is below
set level *) or
external START
disappears
t1 and t2 and
t2MPh will be
stopped (reset) if
t1 and (t2 or
t2MPh) and 150ms
expires and
CBCLDLx input
has logical value
zero
t1 and (t2 or
t2MPh) and 150ms
expires and
CBCLDLx input
has logical value
zero
181