ABB Relion 670 Series Applications Manual page 560

Bay control
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 21
Station communication
Using PTP for synchronizing the MU
IEC17000040 V1 EN-US
Figure 267: Setting example with PTP synchronization
Settings on the local HMI under Main menu/Configuration/Time/Synchronization/
TIMESYNCHGEN:1/IEC61850-9-2:
HwSyncSrc : is not used as the SW-time and HW-time are connected with each other due to
PTP
SyncLostMode : set to Block to block protection functions if time synchronization is lost
or set to
common synchronization is lost
SyncAccLevel : can be set to 1μs since this corresponds to a maximum phase angle error of
0.018 degrees at 50Hz
Settings on the local HMI under Main menu/Configuration/Communication/Ethernet
configuration/Access point/AP_X:
Operation: On
PTP: On
Two status monitoring signals can be:
SYNCH signal on the MUx function block indicates that protection functions are blocked
due to loss of internal time synchronization to the IED
MUSYNCH signal on the MUx function block monitors the synchronization flag
in the datastream and IED hardware time synchronization.
554
IED
9-2
SAM600 TS
SAM600 VT
BlockOnLostUTC if the protection functions are to be blocked when global
© Copyright 2017 Hitachi Power Grids. All rights reserved
PTP
SAM600 CT
IEC17000040-1-en.vsdx
1MRK 511 401-UEN Rev. K
smpSynch
Bay control REC670
Application manual