1MRK 511 401-UEN Rev. K
19.2.3
Setting guidelines
The parameters are set via the local HMI or PCM600.
The following settings can be done for the energy calculation and demand handling function
ETPMMTR:
GlobalBaseSel : Selects the global base value group used by the function to define IBase , UBase
SBase . Note that this function will only use IBase value.
and
Operation : Off / On
EnaAcc : Off / On is used to switch the accumulation of energy on and off.
tEnergy : Time interval when energy is measured.
tEnergyOnPls : gives the pulse length ON time of the pulse. It should be at least 100 ms when
connected to the Pulse counter function block. Typical value can be
tEnergyOffPls : gives the OFF time between pulses. Typical value can be 100 ms.
EAFAccPlsQty and EARAccPlsQty : gives the MWh value in each pulse. It should be selected
together with the setting of the Pulse counter (PCGGIO) settings to give the correct total pulse
value.
ERFAccPlsQty and ERVAccPlsQty : gives the MVArh value in each pulse. It should be selected
together with the setting of the Pulse counter (PCGGIO) settings to give the correct total pulse
value.
For the advanced user there are a number of settings for direction, zero clamping, max limit,
and so on. Normally, the default values are suitable for these parameters.
Bay control REC670
Application manual
© Copyright 2017 Hitachi Power Grids. All rights reserved
Section 19
Metering
SEMOD175556-4 v6
100 ms.
535