Section 24
Basic IED functions
FirmwareVer
ProductVer
IEDMainFunType
SerialNo
OrderingNo
ProductionDate
24.3
Measured value expander block RANGE_XP
24.3.1
Identification
Function description
Measured value expander block
24.3.2
Application
The current and voltage measurements functions (CVMMXN, CMMXU, VMMXU and VNMMXU),
current and voltage sequence measurement functions (CMSQI and VMSQI) and IEC 61850
generic communication I/O functions (MVGAPC) are provided with measurement supervision
functionality. All measured values can be supervised with four settable limits, that is low-low
limit, low limit, high limit and high-high limit. The measure value expander block ( RANGE_XP)
has been introduced to be able to translate the integer output signal from the measuring
functions to 5 binary signals, that is below low-low limit, below low limit, normal, above high-
high limit or above high limit. The output signals can be used as conditions in the configurable
logic.
24.3.3
Setting guidelines
There are no settable parameters for the measured value expander block function.
582
Describes the release number from the production. Example:
Describes the firmware version.
The firmware version can be checked from Main menu/Diagnostics/IED status/
Product identifiers
Firmware version numbers run independently from the release production numbers.
For every release number there can be one or more firmware versions depending on
the small issues corrected in between releases.
Describes the product version. Example:
1
is the Major version of the manufactured product this means, new platform of the product
2 is the Minor version of the manufactured product this means, new functions or new hardware
added to the product
3 is the Major revision of the manufactured product this means, functions or hardware is either
changed or enhanced in the product
Main function type code according to IEC 60870-5-103. Example: 128 (meaning line
protection).
© Copyright 2017 Hitachi Power Grids. All rights reserved
2.1.0
IEC 61850
IEC 60617
identification
identification
RANGE_XP
-
1MRK 511 401-UEN Rev. K
2.1.0
SEMOD52451-1 v2
SEMOD113212-2 v3
ANSI/IEEE C37.2
device number
-
SEMOD52434-4 v6
SEMOD113223-4 v1
Bay control REC670
Application manual