ABB Relion 670 Series Applications Manual page 135

Bay control
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 511 401-UEN Rev. K
~
IEC09000023 V1 EN-US
Figure 57: Through fault current from B to A: I
The IED must not trip for any of the two through-fault currents. Hence the minimum
theoretical current setting (Imin) will be:
³
Imin
MAX I
EQUATION78 V1 EN-US
A safety margin of 5% for the maximum protection static inaccuracy and a safety margin of
5% for the maximum possible transient overreach have to be introduced. An additional 20% is
suggested due to the inaccuracy of the instrument transformers under transient conditions
and inaccuracy in the system data.
The minimum primary setting (Is) for the instantaneous phase overcurrent protection is then:
³
I
1.3
s
EQUATION79 V3 EN-US
The protection function can be used for the specific application only if this setting value is
equal to or less than the maximum fault current that the IED has to clear, I
~
IEC09000024 V1 EN-US
Figure 58: Fault current: I
>>=
IP
EQUATION1147 V3 EN-US
Bay control REC670
Application manual
A
Z
A
IED
Fault
,
(
I
)
fA
fB
×
I
min
I
F
A
Z
A
IED
F
Is
×
100
IBase
© Copyright 2017 Hitachi Power Grids. All rights reserved
I
fA
B
Z
L
fA
B
Z
Z
L
B
Fault
Current protection
Z
~
B
IEC09000023-1-en.vsd
(Equation 24)
(Equation 25)
in Figure 58.
F
~
IEC09000024-1-en.vsd
(Equation 26)
Section 8
129