Section 15
Control
GOOSE over process bus
IEC16000070 V1 EN-US
Figure 156: Signal flow between apparatus control functions with XCBR and XSWI located
Control operation can be performed from the local IED HMI. If users are defined in the IED,
then the local/remote switch is under authority control, otherwise the default user can
perform control operations from the local IED HMI without logging in. The default position of
the local/remote switch is on remote.
Accepted originator categories for PSTO
If the requested command is accepted by the authority control, the value will change.
Otherwise the attribute
value is changed during a command, then the command is aborted.
350
Bay level IED
QCBAY
SCILO
GOOSEXLNRCV
SCILO
GOOSEXLNRCV
Merging Unit
XCBR
XCBR
in a breaker IED
blocked-by-switching-hierarchy is set in the cause signal. If the PSTO
© Copyright 2017 Hitachi Power Grids. All rights reserved
XLNPROXY
XLNPROXY
XCBR
XSWI
1MRK 511 401-UEN Rev. K
IEC 61850 on
station bus
SCSWI
SCSWI
-QB1
-QA1
-QB9
IEC16000070-1-EN.vsdx
Bay control REC670
Application manual