ABB Relion 670 Series Applications Manual page 123

Bay control
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 511 401-UEN Rev. K
Table 17:
Operating
voltage
U>Trip
20 V
40 V
60 V
80 V
100 V
150 V
200 V
Table 18:
Operating
voltage
U>Trip
20 V
40 V
60 V
80 V
100 V
150 V
200 V
The current transformer saturation voltage must be at least 2 ˣ
operating margin. This must be checked after calculation of
When the R value has been selected and the
scheme
according to equation 17.
= ×
IP
n IR
EQUATION1747 V1 EN-US
where:
n
IP
IR
Ires
ΣImag
It should be remembered that the vectorial sum of the currents must be used (IEDs, Metrosil
and resistor currents are resistive). The current measurement is insensitive to DC component
in fault current to allow the use of only the AC components of the fault current in the above
calculations.
The voltage dependent resistor (Metrosil) characteristic is shown in Figure 55.
Bay control REC670
Application manual
1 A channels: input with minimum operating down to 40 mA
Stabilizing
Operating
resistor R
current level
ohms
1 A
500
0.040 A
1000
0.040 A
1500
0.040 A
2000
0.040 A
2500
0.040 A
3750
0.040 A
5000
0.040 A
5 A channels: input with minimum operating down to 100 mA
Stabilizing
Operating
resistor R1
current level
ohms
5 A
200
0.100 A
400
0.100 A
600
0.100 A
800
0.100 A
1000
0.100 A
1500
0.100 A
2000
0.100 A
IP can be calculated. The IED sensitivity is decided by the total current in the circuit
å
+
+
(
Ires
lmag
)
is the CT ratio
primary current at IED pickup,
IED pickup current (U>Trip/SeriesResistor)
is the current through the voltage limiter and
is the sum of the magnetizing currents from all CTs in the circuit (for example, 4 for
restricted earth fault protection, 2 for reactor differential protection, 3-5 for
autotransformer differential protection).
© Copyright 2017 Hitachi Power Grids. All rights reserved
Stabilizing
Operating
resistor R
current level
ohms
1 A
--
--
--
--
600
0.100 A
800
0.100 A
1000
0.100 A
1500
0.100 A
2000
0.100 A
Stabilizing
Operating
resistor R1
current level
ohms
5 A
100
0.200 A
200
0.200 A
300
0.200 A
400
0.200 A
500
0.200 A
750
0.200 A
1000
0.200 A
U>Trip .
U>Trip value has been set, the sensitivity of the
Differential protection
Stabilizing
Operating
resistor R1
current level
ohms
5 A
--
--
100
0.400
150
0.400 A
200
0.400 A
250
0.400 A
375
0.400 A
500
0.400 A
U>Trip to have sufficient
(Equation 17)
Section 7
117

Advertisement

Table of Contents
loading