ABB Relion 670 Series Applications Manual page 481

Bay control
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 511 401-UEN Rev. K
XLowLowLim : Low-low limit. Set as % of YBase (Y is SBase for S,P,Q UBase for Voltage
measurement and
XLimHyst : Hysteresis value in % of range and is common for all limits.
All phase angles are presented in relation to defined reference channel. The parameter
PhaseAngleRef defines the reference, see Section
Calibration curves
It is possible to calibrate the functions (CVMMXN, CMMXU, VMMXU and VNMMXU) to get class
0.5 presentations of currents, voltages and powers. This is accomplished by amplitude and
angle compensation at 5, 30 and 100% of rated current and voltage. The compensation curve
will have the characteristic for amplitude and angle compensation of currents as shown in
figure
240
curve for calculation of factors. The factors will then be used for all related channels.
IEC05000652 V2 EN-US
Figure 240: Calibration curves
18.1.4.1
Setting examples
Three setting examples, in connection to Measurement function (CVMMXN), are provided:
Measurement function (CVMMXN) application for a OHL
Measurement function (CVMMXN) application on the secondary side of a transformer
Measurement function (CVMMXN) application for a generator
For each of them detail explanation and final list of selected setting parameters values will be
provided.
Bay control REC670
Application manual
IBase for current measurement).
(example). The first phase will be used as reference channel and compared with the
© Copyright 2017 Hitachi Power Grids. All rights reserved
"Analog
inputs".
Section 18
Monitoring
SEMOD54481-4 v5
475