ABB Relion 670 Series Applications Manual page 438

Bay control
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 15
Control
output point, send a control-code of latch-On, latch-Off, pulse-On, pulse-Off, Trip or Close. The
remaining parameters are regarded as appropriate. For example, pulse-On, on-time=100, off-
time=300, count=5 would give 5 positive 100 ms pulses, 300 ms apart.
For description of the DNP3 protocol implementation, refer to the Communication manual.
15.10.3
Setting guidelines
AUTOBITS function block has one setting, (
function. These names will be seen in the DNP3 communication management tool in PCM600.
15.11
Single command, 16 signals SINGLECMD
15.11.1
Identification
Function description
Single command, 16 signals
15.11.2
Application
Single command, 16 signals (SINGLECMD) is a common function and always included in the
IED.
The IEDs may be provided with a function to receive commands either from a substation
automation system or from the local HMI. That receiving function block has outputs that can
be used, for example, to control high voltage apparatuses in switchyards. For local control
functions, the local HMI can also be used. Together with the configuration logic circuits, the
user can govern pulses or steady output signals for control purposes within the IED or via
binary outputs.
Figure
220
configuration logic circuit to control a high-voltage apparatus. This type of command control
is normally carried out by sending a pulse to the binary outputs of the IED. Figure
close operation. An open breaker operation is performed in a similar way but without the
synchro-check condition.
432
shows an application example of how the user can connect SINGLECMD via
This function is only used for SPA and LON communication.
© Copyright 2017 Hitachi Power Grids. All rights reserved
Operation : On / Off ) enabling or disabling the
IEC 61850
IEC 60617
identification
identification
SINGLECMD
-
1MRK 511 401-UEN Rev. K
SEMOD158639-5 v3
SEMOD119849-1 v2
GUID-2217CCC2-5581-407F-A4BC-266CD6808984 v1
ANSI/IEEE C37.2
device number
-
220
shows a
Bay control REC670
Application manual
M12445-3 v4