Section 7
Differential protection
It can clearly be seen that the sensitivity is not so much influenced by the selected voltage level
so a sufficient margin should be used. The selection of the stabilizing resistor and the level of
the magnetizing current (mostly dependent of the number of turns) are the most important
factors.
7.1.4.4
Tertiary reactor protection
Reactive power equipment (for example shunt reactors and/or shunt capacitors) can be
connected to the tertiary winding of the power transformers. The 1Ph High impedance
differential protection function HZPDIF can be used to protect the tertiary reactor for phase
faults as well as earth faults if the power system of the tertiary winding is direct or low
impedance earthed.
3·Id
IEC05000176 V3 EN-US
Figure 54: Application of the1Ph High impedance differential protection HZPDIF function on a reactor
124
© Copyright 2017 Hitachi Power Grids. All rights reserved
1MRK 511 401-UEN Rev. K
M16850-118 v5
IEC05000176-3-en.vsd
Bay control REC670
Application manual