Section 10
Unbalance protection
Differential CT
IEC19000197 V1 EN-US
Figure 110: Grounded/ungrounded single WYE connected SCB with CT arrangement
For a grounded/ungrounded H-bridge connection, each phase is divided into two main strings
and the midpoints of the strings are tied together. The unbalance current flowing through the
common point can be measured by using a normal CT.
L1
L2
L3
Strings
IEC19000198 V1 EN-US
Figure 111: Grounded/ungrounded H-bridge connected SCB with CT arrangement