ABB Relion 670 Series Applications Manual page 70

Bay control
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 4
Analog inputs
IEC05000462 V2 EN-US
Figure 10: Example how to set CTStarPoint parameters in the IED
64
Transformer
Transformer and
Line protection
Setting of current input
for transformer functions:
for transformer functions:
Set parameter
CTStarPoint with
Transformer as
reference object.
Correct setting is
"ToObject"
© Copyright 2017 Hitachi Power Grids. All rights reserved
IED
Setting of current input
Setting of current input
Set parameter
CTStarPoint with
Transformer as
reference object.
Correct setting is
"ToObject"
1MRK 511 401-UEN Rev. K
Line
Reverse
Forward
Definition of direction
for directional
line functions
for line functions:
Set parameter
CTStarPoint with
Line as
reference object.
Correct setting is
"FromObject"
Bay control REC670
Application manual