ABB Relion 670 Series Applications Manual page 571

Bay control
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 511 401-UEN Rev. K
21.6.2
Settings
21.6.2.1
Settings for RS485 and optical serial communication
General settings
SPA, DNP and IEC 60870-5-103 can be configured to operate on the SLM optical serial port
while DNP and IEC 60870-5-103 additionally can utilize the RS485 port. A single protocol can be
active on a given physical port at any time.
Two different areas in the HMI are used to configure the IEC 60870-5-103 protocol.
1.
The port specific IEC 60870-5-103 protocol parameters are configured under:
Main menu/Configuration/Communication/Station Communication/IEC60870-5-103/
<config-selector> is:
2.
The protocol to activate on a physical port is selected under:
Main menu/Configuration/Communication/Station Communication/Port
configuration/
GUID-CD4EB23C-65E7-4ED5-AFB1-A9D5E9EE7CA8 V3 EN-US
Figure 275: Settings for IEC 60870-5-103 communication
The general settings for IEC 60870-5-103 communication are the following:
SlaveAddress and BaudRate : Settings for slave number and communication speed (baud
rate).
Bay control REC670
Application manual
<config-selector>
SlaveAddress
BaudRate
RevPolarity (optical channel only)
CycMeasRepTime
MasterTimeDomain
TimeSyncMode
EvalTimeAccuracy
EventRepMode
CmdMode
RepIntermediatePos
"OPTICAL103:1" for the optical serial channel on the SLM
"RS485103:1" for the RS485 port
RS485 port
RS485PROT:1 (off, DNP, IEC103)
SLM optical serial port
PROTOCOL:1 (off, DNP, IEC103, SPA)
GUID-CD4EB23C-65E7-4ED5-AFB1-A9D5E9EE7CA8 V3 EN
© Copyright 2017 Hitachi Power Grids. All rights reserved
Section 21
Station communication
M17109-116 v1
M17109-118 v13
565