1MRK 511 401-UEN Rev. K
15.4.3.4
Signals from bus-coupler
If the busbar is divided by bus-section disconnectors into bus-sections, the signals BC_12 from
the busbar coupler of the other busbar section must be transmitted to the own busbar coupler
if both disconnectors are closed.
(WA1)A1
(WA2)B1
(WA7)C
IEC04000484 V1 EN-US
Figure 172: Busbars divided by bus-section disconnectors (circuit breakers)
To derive the signals:
Signal
BC_12_CL
VP_BC_12
EXDU_BC
These signals from each bus-coupler bay (ABC_BC), except the own bay, are needed:
Signal
BC12CLTR
VPBC12TR
EXDU_BC
These signals from each bus-section disconnector bay (A1A2_DC) are also needed. For
B1B2_DC, corresponding signals from busbar B are used. The same type of module (A1A2_DC)
is used for different busbars, that is, for both bus-section disconnector A1A2_DC and B1B2_DC.
Signal
DCCLTR
VPDCTR
EXDU_DC
If the busbar is divided by bus-section circuit breakers, the signals from the bus-section
coupler bay (A1A2_BS), rather than the bus-section disconnector bay (A1A2_DC), must be used.
For B1B2_BS, corresponding signals from busbar B are used. The same type of module
(A1A2_BS) is used for different busbars, that is, for both bus-section circuit breakers A1A2_BS
and B1B2_BS.
Signal
S1S2CLTR
VPS1S2TR
EXDU_BS
For a bus-coupler bay in section 1, these conditions are valid:
Bay control REC670
Application manual
Section 1
A1A2_DC(BS)
B1B2_DC(BS)
ABC_BC
Another bus-coupler connection exists between busbar WA1 and WA2.
The switch status of BC_12 is valid.
No transmission error from any bus-coupler bay (BC).
A bus-coupler connection through the own bus-coupler exists between busbar
WA1 and WA2.
The switch status of BC_12 is valid.
No transmission error from the bay that contains the above information.
The bus-section disconnector is closed.
The switch status of bus-section disconnector DC is valid.
No transmission error from the bay that contains the above information.
A bus-section coupler connection exists between bus sections 1 and 2.
The switch status of bus-section coupler BS is valid.
No transmission error from the bay containing the above information.
© Copyright 2017 Hitachi Power Grids. All rights reserved
Section 2
A2
B2
C
ABC_BC
en04000484.vsd
Section 15
Control
M13553-58 v5
371