ABB Relion 670 Series Applications Manual page 378

Bay control
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 15
Control
VPBC12TR (sect.2)
IEC04000485 V1 EN-US
Figure 173: Signals to a bus-coupler bay in section 1 from a bus-coupler bay in another
For a bus-coupler bay in section 2, the same conditions as above are valid by changing section
1 to section 2 and vice versa.
15.4.3.5
Configuration setting
If there is no bypass busbar and therefore no QB2 and QB7 disconnectors, then the
interlocking for QB2 and QB7 is not used. The states for QB2, QB7, QC71 are set to open by
setting the appropriate module inputs as follows. In the functional block diagram, 0 and 1 are
designated 0=FALSE and 1=TRUE:
QB2_OP = 1
QB2_CL = 0
QB7_OP = 1
QB7_CL = 0
QC71_OP = 1
QC71_CL = 0
If there is no second busbar B and therefore no QB2 and QB20 disconnectors, then the
interlocking for QB2 and QB20 are not used. The states for QB2, QB20, QC21, BC_12, BBTR are
set to open by setting the appropriate module inputs as follows. In the functional block
diagram, 0 and 1 are designated 0=FALSE and 1=TRUE:
QB2_OP = 1
QB2_CL = 0
QB20_OP = 1
QB20_CL = 0
QC21_OP = 1
QC21_CL = 0
BC_12_CL = 0
VP_BC_12 = 1
BBTR_OP = 1
VP_BBTR = 1
15.4.4
Interlocking for transformer bay AB_TRAFO
372
DCCLTR (A1A2)
DCCLTR (B1B2)
BC12CLTR (sect.2)
VPDCTR (A1A2)
VPDCTR (B1B2)
EXDU_DC (A1A2)
EXDU_DC (B1B2)
EXDU_BC (sect.2)
section
© Copyright 2017 Hitachi Power Grids. All rights reserved
BC_12_CL
&
VP_BC_12
&
EXDU_BC
&
en04000485.vsd
1MRK 511 401-UEN Rev. K
M13553-107 v4
IP14149-1 v2
Bay control REC670