1MRK 511 401-UEN Rev. K
Using MU for time synchronization via PPS
IEC/UCA 61850-9-2LE
IEC10000061 V2 EN-US
Figure 268: Setting example when MU is the synchronizing source
Settings on the local HMI under Main menu/Configuration/Time/Synchronization/
TIMESYNCHGEN:1/IEC61850-9-2:
HwSyncSrc : set to PPS as generated by the MU (ABB MU)
SyncLostMode : set to Block to block protection functions if time synchronization is lost
SyncAccLevel : can be set to 4μs since this corresponds to a maximum phase angle error of
0.072 degrees at 50Hz
Settings on the local HMI under Main menu/Configuration/Time/Synchronization/
TIMESYNCHGEN:1/General:
fineSyncSource can be set to something different to correlate events and data to other
IEDs in the station.
Two status monitoring signals can be:
SYNCH signal on the MUx function block indicates that protection functions are blocked
due to loss of internal time synchronization to the IED.
MUSYNCH signal on the MUx function block monitors the synchronization flag
in the datastream and IED hardware time synchronization.
SMPLLOST indicates that merging unit data are generated by internal substitution or one/
more channel's Quality is not good or merging unit is in Testmode/detailed quality=Test, IED
is not in test mode.
Using external clock for time synchronization
Bay control REC670
Application manual
This example is not valid when GPS time is used for differential protection,
when PTP is enabled or when the PMU report is used.
IED
Analog data
MU
This example is not valid when GPS time is used for differential protection,
when PTP is enabled or when the PMU report is used.
© Copyright 2017 Hitachi Power Grids. All rights reserved
PPS
Synchronization
IEC10000061=2=en=Original.vsd
Section 21
Station communication
smpSynch
555