1MRK 511 401-UEN Rev. K
9.4
Voltage differential protection VDCPTOV
9.4.1
Identification
Function description
Voltage differential protection
9.4.2
Application
The Voltage differential protection VDCPTOV functions can be used in some different
applications.
Voltage unbalance protection for capacitor banks. The voltage on the bus is supervised
with the voltage in the capacitor bank, phase- by phase. Difference indicates a fault, either
short-circuited or open element in the capacitor bank. It is mainly used on elements with
external fuses but can also be used on elements with internal fuses instead of a current
unbalance protection measuring the current between the neutrals of two half's of the
capacitor bank. The function requires voltage transformers in all phases of the capacitor
bank. Figure
Ph L3
IEC06000390 V3 EN-US
Figure 103: Connection of voltage differential protection VDCPTOV function to detect
VDCPTOV function has a block input (BLOCK) where a fuse failure supervision (or MCB tripped)
can be connected to prevent problems if one fuse in the capacitor bank voltage transformer
Bay control REC670
Application manual
103
shows some different alternative connections of this function.
U1
Ud>L1
U2
Ph L3
Ph L2
unbalance in capacitor banks (one phase only is shown)
© Copyright 2017 Hitachi Power Grids. All rights reserved
IEC 61850
IEC 60617
identification
identification
VDCPTOV
-
Single earthed wye
Ph L2
Ud>L1
U1
U2
Ph L3
IEC06000390_1_en.vsd
Voltage protection
SEMOD153860-1 v2
SEMOD167723-2 v2
ANSI/IEEE C37.2
device number
60
SEMOD153893-5 v4
Double wye
Ph L2
Section 9
223