ABB Relion 670 Series Applications Manual page 112

Bay control
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 6
Wide area measurement system
IEC140000128 V2 EN-US
Figure 43: An example of wrong connection of SMAI and PHASORREPORT blocks in ACT
Rule 3:
This rule is only related to the connection of 3PHSUM block to the PHASORREPORT block. If
3PHSUM block is configured to use external DFT reference (from SMAI reference block), it shall
only be connected to the same PHASORREPORT block instance as the one the SMAI reference
block is connected to. In other words, both the SMAI reference block and 3PHSUM block
(3PHSUM block with external DFT reference) shall be connected to the same instance of
PHASORREPORT block (PHASOR1-32 of Instance number 1 or 2).
Figure
44
ACT where SMAI3 is configured as the reference block for DFT reference external out
(DFTRefExtOut) and 3PHSUM uses external DFT reference (from SMAI3). Figures
show the corresponding setting parameters.
IEC140000129 V2 EN-US
Figure 44: An example of correct connection of 3PHSUM and PHASORREPORT blocks in
106
shows an example of correct connection of 3PHSUM and PHASORREPORT blocks in
ACT
© Copyright 2017 Hitachi Power Grids. All rights reserved
1MRK 511 401-UEN Rev. K
IEC140000128-2-en.vsd
45
and
46
IEC140000129-2-en.vsd
Bay control REC670
Application manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion rec670

Table of Contents