1MRK 511 401-UEN Rev. K
•
The capacitance of a healthy unit can be calculated as follows:
C
u
IECEQUATION19122 V1 EN-US
•
If an element fails in the unit, the capacitance of the unit changes to:
C
x
IECEQUATION19123 V1 EN-US
Where,
C
is the capacitance of the faulty unit
x
F
is the number of elements failed in a unit (F
e
•
The capacitance of the faulty section can be calculated as follows:
=
C
1
IECEQUATION19124 V1 EN-US
•
The capacitance of the healthy section can be calculated as follows:
C
2
IECEQUATION19125 V1 EN-US
•
The capacitance of phase L1 can be calculated as follows:
C
L
IECEQUATION19222 V1 EN-US
•
For a grounded capacitor bank configuration, the differential voltage is calculated by
using the bus voltage and tap voltage from the bank with the corresponding voltage ratio
for phase L1 as follows:
U
TapL
IECEQUATION19126 V1 EN-US
UDIFL
IECEQUATION19217 V1 EN-US
Where,
U
L1
U
TapL1
UDIFL1 is the differential voltage of phase L1
•
The differential phase voltages are expressed in percentage of base voltage UBase as
follows:
PUDIFLx
IECEQUATION19376 V1 EN-US
Bay control REC670
Application manual
P
=
´
=
e
C
4.6667
C
e
e
S
e
æ
ö
(
)
Pe
-
´
ç
P
F
÷
e
e
-
S
1
ç
÷
=
´
e
C
ç
÷
P
(
)
-
+
e
P
F
ç
÷
e
e
-
è
ø
S
1
e
C
x
P C
4.6667
C
u
u
e
æ
ö
´
C C
= ç
÷
1
2
+
è
ø
1
C
C
1
2
æ
ö
C
=
´ ç
1
÷
U
1
L
1
+
è
ø
C
C
1
2
1
1
U
L
1
USEDURATL
1
is the measured bus voltage of phase L1
is the measured tap voltage of phase L1
UDIFLx
=
´
100
UBase
3
© Copyright 2017 Hitachi Power Grids. All rights reserved
e
= 0, 1, 2, ...13)
e
U
TapL
1
Section 10
Unbalance protection
(Equation 128)
(Equation 129)
(Equation 130)
(Equation 131)
(Equation 132)
(Equation 133)
(Equation 134)
(Equation 135)
255