Section 15
Control
IEC13000016 V2 EN-US
Figure 157: APC - Local remote function block
15.3.4
Switch controller SCSWI
SCSWI may handle and operate on one three-phase device or three one-phase switching
devices.
After the selection of an apparatus and before the execution, the switch controller performs
the following checks and actions:
•
A request initiates to reserve other bays to prevent simultaneous operation.
•
Actual position inputs for interlocking information are read and evaluated if the operation
is permitted.
•
The synchrocheck/synchronizing conditions are read and checked, and performs
operation upon positive response.
•
The blocking conditions are evaluated
•
The position indications are evaluated according to given command and its requested
direction (open or closed).
The command sequence is supervised regarding the time between:
•
Select and execute.
•
Select and until the reservation is granted.
•
Execute and the final end position of the apparatus.
•
Execute and valid close conditions from the synchrocheck.
At error the command sequence is cancelled.
In the case when there are three one-phase switches (SXCBR/SXSWI) connected to the switch
controller function, the switch controller will "merge" the position of the three switches to the
352
© Copyright 2017 Hitachi Power Grids. All rights reserved
1MRK 511 401-UEN Rev. K
IEC13000016-2-en.vsd
M16596-3 v7
Bay control REC670
Application manual