Section 24
Basic IED functions
example the insertion of the test handle into the test switch with its auxiliary contact is
connected to a BI on the IED and further inside the configuration to the input IED_TEST on the
function block TESTMODE. Another example is when loss of Service Values appears, or as
explained above the setting via the LHMI.
When setting via PST or LHMI the parameter
the function is not executed and the behavior (beh) is set to
override it. When a behavior of a function is
keeps its current state.
The IEC 61850-7-4 gives a detailed overview over all aspects of the test mode and other states
of mode and behavior. The status of a function block behavior
the Main menu/Test/Function status/Function group/Function block descriptive name/LN
name/Outputs.
When the
control commands with a test bit are accepted.
When the
bit are accepted. Outputs to the process via a non-IEC 61850 link data are blocked by the
function block. Only process-related outputs on function blocks related to primary
equipment are blocked. If there is an XCBR function block used, the outputs
and
When the
are accepted. Outputs to the process via a non-IEC 61850 link data are blocked by the
function block. In addition, the function block can be blocked when their
This can be done if the function block has a block input.
The block status of a component is shown on the LHMI as the
Beh: Main menu/Test/Function status/Function group/Function block descriptive
as for
name/LN name/Outputs. If the
24.12.2
Setting guidelines
Remember always that there are two possible ways to place the IED in the
state. If, the IED is set to normal operation (
being in the test mode, the input signal IED_TEST on the TESTMODE function block is
activated in the configuration.
Forcing of binary input and output signals is only possible when the IED is in IED test mode.
24.13
Time synchronization TIMESYNCHGEN
24.13.1
Application
Use time synchronization to achieve a common time base for the IEDs in a protection and
control system. This makes it possible to compare events and disturbance data between all
IEDs in the system. If a global common source (i.e. GPS) is used in different substations for the
time synchronization, also comparisons and analysis between recordings made at different
locations can be easily performed and a more accurate view of the actual sequence of events
can be obtained.
Time-tagging of internal events and disturbances are an excellent help when evaluating faults.
Without time synchronization, only the events within one IED can be compared with each
594
When IEC 61850 Mod of a function is set to
LHMI will be set to flashing to indicate the abnormal operation of the IED.
Beh of a function block is set to Test , the function block is not blocked and all
Beh of a function block is set to Test/blocked , all control commands with a test
EXC_Close are blocked.
Beh of a function block is set to Blocked , all control commands with a test bit
© Copyright 2017 Hitachi Power Grids. All rights reserved
Operation of any function in an IED is set to Off ,
Off the function will not execute. The related Mod
Blk output is not shown, the component cannot be blocked.
TestMode = Off ), but the functions are still shown
1MRK 511 401-UEN Rev. K
Off and it is not possible to
Off or Blocked , the Start LED on the
Beh is shown on the LHMI under
EXC_Open
Beh is blocked .
Blk output under the same path
TestMode = On "
Bay control REC670
Application manual
M15260-3 v7