1MRK 511 401-UEN Rev. K
GOOSEPortEd1 : Selection of the Ethernet link where GOOSE traffic shall be sent and received.
This is only valid for Edition 1 and can be ignored if Edition 2 is used. For Edition 2, the
Ethernet link selection is done with the Ethernet Configuration Tool (ECT) in PCM600.
21.2.3
Horizontal communication via GOOSE
21.2.3.1
Sending data
In addition to the data object and data attributes of the logical nodes, it is possible to send
the outputs of the function blocks using the generic communication blocks. The outputs of
this function can be set in a dataset and be sent in a GOOSE Control Block to other subscriber
IEDs. There are different function blocks for different type of sending data.
Generic communication function for Single Point indication SPGAPC, SP16GAPC
Application
Generic communication function for Single Point Value (SPGAPC) function is used to send one
single logical output to other systems or equipment in the substation. SP16GAPC can be used
to send up to 16 single point values from the application functions running in the same cycle
time. SPGAPC has one visible input and SPGAPC16 has 16 visible inputs that should be
connected in the ACT tool.
Setting guidelines
There are no settings available for the user for SPGAPC.
Generic communication function for Measured Value MVGAPC
Application
Generic communication function for measured values (MVGAPC) function is used to send the
instantaneous value of an analog signal to other systems or equipment in the substation. It
can also be used inside the same IED, to attach a RANGE aspect to an analog value and to
permit measurement supervision on that value.
Setting guidelines
The settings available for Generic communication function for Measured Value (MVGAPC)
function allows the user to choose a deadband and a zero deadband for the monitored signal.
Values within the zero deadband are considered as zero.
The high and low limit settings provides limits for the high-high-, high, normal, low and low-
low ranges of the measured value. The actual range of the measured value is shown on the
range output of MVGAPC function block. When a Measured value expander block (RANGE_XP)
is connected to the range output, the logical outputs of the RANGE_XP are changed
accordingly.
21.2.3.2
Receiving data
The GOOSE data must be received at function blocks. There are different GOOSE receiving
function blocks depending on the type of the received data. Refer to the Engineering manual
for more information about how to configure GOOSE.
Function block type
GOOSEBINRCV
GOOSEINTLKRCV
GOOSEDPRCV
Table continues on next page
Bay control REC670
Application manual
© Copyright 2017 Hitachi Power Grids. All rights reserved
GUID-9888ECAD-8221-4B31-A443-EB1E3A9022C4 v1
GUID-CAE4B020-7131-49BF-BA29-3EEE0EFEA2B8 v2
Data Type
16 single point
2 single points
16 double points
Double point
Section 21
Station communication
SEMOD55999-1 v4
SEMOD55350-5 v8
SEMOD55376-5 v5
SEMOD55402-1 v3
SEMOD55872-5 v10
SEMOD55424-5 v5
545