1MRK 511 401-UEN Rev. K
See chapter "Inverse time characteristics" in Technical Manual for the description of different
characteristics
tPCrv, tACrv, tBCrv, tCCrv : Parameters for customer creation of inverse time characteristic
curve (Curve type = 17). The time characteristic equation is:
æ
ç
ç
[ ] =
t s
ç
ç
è
EQUATION1958 V1 EN-US
tINNonDir is the definite time delay for the non directional earth fault current protection, given
in s.
OpUN> is set On to activate the trip function of the residual over voltage protection.
tUN is the definite time delay for the trip function of the residual voltage protection, given in s.
8.7
Thermal overload protection, one time constant,
Celsius/Fahrenheit LCPTTR/LFPTTR
8.7.1
Identification
Function description
Thermal overload protection, one
time constant, Celsius
Thermal overload protection, one
time constant, Fahrenheit
8.7.2
Application
Lines and cables in the power system are designed for a certain maximum load current level. If
the current exceeds this level the losses will be higher than expected. As a consequence the
temperature of the conductors will increase. If the temperature of the lines and cables reaches
too high values the equipment might be damaged:
The sag of overhead lines can reach unacceptable value.
If the temperature of conductors, for example aluminium conductors, gets too high the
material will be destroyed.
In cables the insulation can be damaged as a consequence of the overtemperature. As a
consequence of this phase to phase or phase to earth faults can occur.
In stressed situations in the power system it can be required to overload lines and cables for a
limited time. This should be done while managing the risks safely.
Bay control REC670
Application manual
ö
÷
A
÷
+
×
B
InMult
÷
p
æ
ö
i
-
C
ç
÷
÷
è
>
ø
ø
in
© Copyright 2017 Hitachi Power Grids. All rights reserved
IEC 61850
IEC 60617
identification
identification
LCPTTR
LFPTTR
Section 8
Current protection
(Equation 63)
ANSI/IEEE C37.2
device number
26
26
IP14512-1 v7
M17106-1 v7
M15283-3 v9
169

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion rec670

Table of Contents