Section 22
Remote communication
Blocked
OutOfService
TerminalNo is used to assign a unique address to each LDCM in all current differential IEDs. Up
to 256 LDCMs can be assigned a unique number. For example, in a local IED with two LDCMs:
LDCM for slot 305: set
LDCM for slot 306: set
In multiterminal current differential applications,with 4 LDCMs in each IED, up to 20 unique
addresses must be set.
RemoteTermNo is used to assign a number to each related LDCM in the remote IED. For each
RemoteTermNo is set to a different value than TerminalNo , but equal to the TerminalNo
LDCM,
of the remote end LDCM. In the remote IED,
follows:
LDCM for slot 305: set
LDCM for slot 306: set
DiffSync defines the method of time synchronization for the line differential function: Echo or
GPS .
GPSSyncErr : when GPS synchronization is lost, synchronization of the line differential function
continues for 16 s based on the stability in the local IED clocks. After that, setting
the line differential function or setting
method.
CommSync defines the Master and Slave relation in the communication system, and should
not be mistaken for the synchronization of line differential current samples. When direct fiber
is used, one LDCM is set as
used, the IED is always set as
master.
OptoPower has two settings: LowPower and HighPower .
Short-range LDCM: Use
km.
Medium-range LDCM: Typical distance 80 km for
572
IED does not use data from the LDCM
IED informs the remote end that it is out of service
TerminalNo to 1 and RemoteTermNo to 2
TerminalNo to 3 and RemoteTermNo to 4
A unique address is necessary to give high security against incorrect
addressing in the communication system. If the same number is used for
TerminalNo in some of the LDCMs, a loop-back test in the communication
system can give an incorrect trip.
TerminalNo to 2 and RemoteTermNo to 1
TerminalNo to 4 and RemoteTermNo to 3
The redundant channel is always configured to the lower position, for example:
Slot 305: main channel
Slot 306: redundant channel
The same is applicable for slot 312-313 and slot 322-323.
Using
Echo in this case is safe only if there is no risk of varying transmission
asymmetry.
Echo in this case is safe only if there is no risk of varying transmission
Using
asymmetry.
Master and the other as Slave . When a modem and multiplexer is
Slave because the telecommunication system provides the clock
LowPower for fibers 0 – 1 km and HighPower for fibers greater than 1
© Copyright 2017 Hitachi Power Grids. All rights reserved
TerminalNo and RemoteTermNo are reversed as
Echo keeps it on by using the Echo synchronization
HighPower .
1MRK 511 401-UEN Rev. K
Block blocks
Bay control REC670
Application manual