ABB Relion 670 Series Applications Manual page 83

Bay control
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 511 401-UEN Rev. K
Where:
1)
2)
3)
4)
5)
4.2.4.4
Example on how to connect a phase-to-phase connected VT to the IED
Figure
22
an overview of the required actions by the user in order to make this measurement available to
the built-in protection and control functions within the IED. It shall be noted that this VT
connection is only used on lower voltage levels (that is, rated primary voltage below 40 kV).
Bay control REC670
Application manual
shows how to connect three secondary phase-to-earth voltages to three VT inputs on the IED
is the TRM where these three voltage inputs are located. For these three voltage inputs, the
following setting values shall be entered:
VTprim = 132 kV
VTsec = 110 V
Inside the IED, only the ratio of these two parameters is used. It shall be noted that the ratio of
the entered values exactly corresponds to ratio of one individual VT.
66
66
3
=
110
110
3
EQUATION1903 V1 EN-US
are three connections made in Signal Matrix Tool (SMT), which connect these three voltage
inputs to first three input channels of the preprocessing function block 5). Depending on the
type of functions which need this voltage information, more then one preprocessing block might
be connected in parallel to these three VT inputs.
shows that in this example the fourth (that is, residual) input channel of the preprocessing block
is not connected in SMT tool. Thus the preprocessing block will automatically calculate 3Uo
inside by vectorial sum from the three phase to earth voltages connected to the first three input
channels of the same preprocessing block. Alternatively, the fourth input channel can be
connected to open delta VT input, as shown in Figure 23.
is a Preprocessing block that has the task to digitally filter the connected analog inputs and
calculate:
fundamental frequency phasors for all input channels
harmonic content for all input channels
positive, negative and zero sequence quantities by using the fundamental frequency
phasors for the first three input channels (channel one taken as reference for sequence
quantities)
These calculated values are then available for all built-in protection and control functions within
the IED, which are connected to this preprocessing function block in the configuration tool. For
this application most of the preprocessing settings can be left to the default values. However the
following settings shall be set as shown here:
UBase=66 kV (that is, rated Ph-Ph voltage)
If frequency tracking and compensation is required (this feature is typically required only for IEDs
installed in the generating stations) then the setting parameters
accordingly.
gives an example how to connect a phase-to-phase connected VT to the IED. It gives
© Copyright 2017 Hitachi Power Grids. All rights reserved
Section 4
Analog inputs
(Equation 2)
DFTReference shall be set
SEMOD55055-134 v7
77

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion rec670

Table of Contents