ABB Relion 670 Series Applications Manual page 189

Bay control
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 511 401-UEN Rev. K
No.
StartMode
21
LatchedStart
22
FollowStart
23
FollowStart
24
FollowStart
25
FollowStart&
Mode
Table continues on next page
Bay control REC670
Application manual
RetripMode
t1 and t2 initiated
with
Always
external START
Off
external START
UseFunction
external START
Mode
Always
external START
Off
external START
and current above
set level
© Copyright 2017 Hitachi Power Grids. All rights reserved
When t1 has
When t2 or t2MPh
elapsed, TRRET will
has elapsed, TRBU
will be given if
always be given
current is above
set level *) and
higher than
I>BlkCBPos or
CBCLDLx input
has logical value
one when current
is smaller than
I>BlkCBPos
never be given
current is above
set level *) and
higher than
I>BlkCBPos or
CBCLDLx input
has logical value
one when current
is smaller than
I>BlkCBPos
be given if current
current is above
is above set level
set level *) and
of IPh> and higher
higher than
than I>BlkCBPos or
I>BlkCBPos or
CBCLDLx input has
CBCLDLx input
logical value one
has logical value
when current is
one when current
smaller than
is smaller than
I>BlkCBPos
I>BlkCBPos
be given if external
current is above
START is present
set level *) and
higher than
I>BlkCBPos or
CBCLDLx input
has logical value
one when current
is smaller than
I>BlkCBPos
never be given
current is above
set level *) and
higher than
I>BlkCBPos or
CBCLDLx input
has logical value
one when current
is smaller than
I>BlkCBPos
Section 8
Current protection
t1 and t2 and
t2MPh will be
stopped (reset) if
t1 and (t2 or
t2MPh) and 150ms
expires and
current is below
set level *) or
CBCLDLx input
has logical value
zero
external START
disappears
external START
disappears
external START
disappears
current is below
set level *) or
external START
disappears
183