Custom U/F Ratio - ABB ACS355 series User Manual

Hide thumbs Also See for ACS355 series:
Table of Contents

Advertisement

Custom U/f ratio

The user can define a U/f curve (output voltage as a function of frequency). This
custom ratio is used only in special applications where linear and squared U/f ratio
are not sufficient (eg, when motor break-away torque needs to be boosted).
Voltage (V)
Par.
2618
Par.
2616
Par.
2614
Par.
2612
Par.
2610
Par.
2603
Note: The U/f curve can be used in scalar control only, ie, when
MODE
setting is
SCALAR:
Note: The voltage and the frequency points of the U/f curve must fulfill the following
requirements:
2610
<
2612
<
2614
2611
<
2613
<
2615
WARNING! High voltage at low frequencies may result in poor performance or
motor damage (overheating).
Settings
Parameter
2605
2610...2618
Diagnostics
Fault
PAR USER U/F
Par.
2611
Par.
2613
FREQ.
<
2616
<
2618
and
<
2617
<
9907
Additional information
Custom U/f ratio activation
Custom U/f ratio settings
Additional information
Incorrect U/f ratio
Custom U/f ratio
Par.
2615
Program features 143
Par.
2617
Par.
9907
9904 MOTOR CTRL
f (Hz)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents