ABB ACS355 series User Manual page 231

Hide thumbs Also See for ACS355 series:
Table of Contents

Advertisement

All parameters
No.
Name/Value
2109 EMERG STOP
SEL
NOT SEL
DI1
DI2
DI3
DI4
DI5
DI1(INV)
DI2(INV)
DI3(INV)
DI4(INV)
DI5(INV)
2110 TORQ BOOST
CURR
15...300%
2111 STOP SIGNAL
DLY
0...10000 ms
Description
Selects the source for the external emergency stop
command.
The drive cannot be restarted before the emergency stop
command is reset.
Note: The installation must include emergency stop devices
and any other safety equipment that may be needed.
Pressing the stop key on the drive's control panel does
NOT:
• generate an emergency stop of the motor
• separate the drive from dangerous potential.
Emergency stop function is not selected
Digital input DI1. 1 = stop along the emergency stop ramp.
See parameter
2208 EMERG DEC
stop command reset.
See selection DI1.
See selection DI1.
See selection DI1.
See selection DI1.
Inverted digital input DI. 0 = stop along the emergency stop
ramp. See parameter
emergency stop command reset
See selection DI1(INV).
See selection DI1(INV).
See selection DI1(INV).
See selection DI1(INV).
Defines the maximum supplied current during torque boost.
See parameter
2101 START
Value as a percentage
Defines the stop signal delay time when parameter
STOP FUNCTION
is set to
Delay time
Actual signals and parameters 231
TIME. 0 = emergency
2208 EMERG DEC
TIME. 1 =
FUNCTION.
SPEED
COMP.
Def/FbEq
NOT SEL
0
1
2
3
4
5
-1
-2
-3
-4
-5
100%
1 = 1%
2102
0 ms
1 = 1 ms