336 Fieldbus control with embedded fieldbus
Bit
Name
8
LIMIT
9
SUPERVISION
10
REV_REF
11
REV_ACT
12
PANEL_LOCAL
13
FIELDBUS_LOCAL
14
EXT2_ACT
15
FAULT
Bit
Name
16
ALARM
17
NOTICE
18
DIRLOCK
19
LOCALLOCK
20
CTL_MODE
21
JOGGING ACTIVE
DCU profile Status word, parameter
Value
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
DCU profile Status word, parameter
Value
1
0
1
0
1
0
1
0
1
0
1
0
0303 FB STS WORD 1
Status
Operation is limited by internal protection limits or
group
20 LIMITS
settings (excluding speed and
frequency limits).
Operation is within internal protection limits and
according group
20 LIMITS
and frequency limits).
A supervised parameter (group
outside its limits.
All supervised parameters are within limits.
Drive reference is in reverse direction.
Drive reference is in forward direction.
Drive is running in reverse direction.
Drive is running in forward direction.
Control is in control panel (or PC tool) local mode.
Control is not in control panel local mode.
Control is in fieldbus local mode
Control is not in fieldbus local mode.
Control is in EXT2 mode.
Control is in EXT1 mode.
Drive is in a fault state.
Drive is not in a fault state.
0304 FB STS WORD 2
Status
An alarm is on.
No alarms are on.
A maintenance request is pending.
No maintenance request
Direction lock is ON. (Direction change is locked.)
Direction lock is OFF.
Local mode lock is ON. (Local mode is locked.)
Local mode lock is OFF.
Drive is in vector control mode.
Drive is in scalar control mode.
Jogging function is active.
Jogging function is not active.
settings (excluding speed
32
SUPERVISION) is