172 Program features

Example 1

50 Hz
0 Hz
-50 Hz
DI1
DI2
Sequence programming is activated by digital input DI1.
ST1: Drive is started in reverse direction with -50 Hz reference and 10 s ramp time.
State 1 is active for 40 s.
ST2: Drive is accelerated to 20 Hz with 60 s ramp time. State 2 is active for 120 s.
ST3: Drive is accelerated to 25 Hz with 5 s ramp time. State 3 is active until the
Sequence programming is disabled or until booster start is activated by DI2.
ST4: Drive is accelerated to 50 Hz with 5 s ramp time. State 4 is active for 200 s and
after that the state shifts back to state 3.
Parameter
1002 EXT2 COMMANDS
1102 EXT1/EXT2 SEL
1106 REF2 SELECT
1601 RUN ENABLE
2102 STOP FUNCTION
2201 ACC/DEC 1/2 SEL
8401 SEQ PROG ENABLE ALWAYS
8402 SEQ PROG START
8404 SEQ PROG RESET
ST1
ST2
Seq. start
Setting
SEQ PROG
EXT2
SEQ PROG
NOT SEL
RAMP
SEQ PROG
DI1
DI1(INV)
ST3
ST4
State change trigger
Additional information
Start, stop, direction commands for EXT2
EXT2 activation
Sequence programming output as REF2
Deactivation of Run enable
Ramp stop
Ramp as defined by parameter 8422/.../8452.
Sequence programming enabled
Sequence programming activation through
digital input (DI1)
Sequence programming reset (ie, reset to state
1, when DI1 signal is lost (1 -> 0)
ST3