210 Actual signals and parameters
All parameters
No.
Name/Value
DI4(INV)
DI5(INV)
1602 PARAMETER
LOCK
LOCKED
OPEN
NOT SAVED
1603 PASS CODE
0...65535
1604 FAULT RESET
SEL
KEYPAD
DI1
DI2
DI3
DI4
DI5
START/STOP
COMM
DI1(INV)
DI2(INV)
Description
See selection DI1(INV).
See selection DI1(INV).
Selects the state of the parameter lock. The lock prevents
parameter changing from the control panel.
Parameter values cannot be changed from the control
panel. The lock can be opened by entering the valid code to
parameter
1603 PASS
The lock does not prevent parameter changes made by
macros or fieldbus.
The lock is open. Parameter values can be changed.
Parameter changes from the control panel are not stored
into the permanent memory. To store changed parameter
values, set parameter
SAVE....
Selects the pass code for the parameter lock (see
parameter
1602 PARAMETER
Pass code. Setting 358 opens the lock. The value reverts
back to 0 automatically.
Selects the source for the fault reset signal. The signal
resets the drive after a fault trip if the cause of the fault no
longer exists.
Fault reset only from the control panel
Reset through digital input DI1 (reset on the rising edge of
DI1) or from the control panel
See selection DI1.
See selection DI1.
See selection DI1.
See selection DI1.
Reset along with the stop signal received through a digital
input, or from the control panel.
Note: Do not use this option when start, stop and direction
commands are received through fieldbus communication.
Fieldbus interface as the source for the fault reset signal, ie,
Control word
0301 FB CMD WORD 1
profile
5319 EFB PAR 19
the fieldbus controller through the fieldbus adapter or
embedded fieldbus (Modbus) to the drive. For the Control
word bits, see sections
333
and
ABB drives communication profile
Reset through inverted digital input DI1 (reset on the falling
edge of DI1) or from the control panel
See selection DI1(INV).
CODE.
1607 PARAM SAVE
LOCK).
bit 4 (with ABB drives
bit 7). The Control word is sent by
DCU communication profile
Def/FbEq
-4
-5
OPEN
0
1
2
value to
0
1 = 1
KEYPAD
0
1
2
3
4
5
7
8
on page
on page 328.
-1
-2