326 Fieldbus control with embedded fieldbus
Modbus register
40034 ACS355 Status
word MSW
Note: Parameter writes through standard Modbus are always volatile, ie, modified
values are not automatically stored to the permanent memory. Use parameter
PARAM SAVE
to save all changed values.

Function codes

Supported function codes for the holding 4xxxx register:
Code
Function name
hex
(dec)
03
Read 4X Register Reads the binary contents of registers (4X references) in a slave
(03)
06
Preset single 4X
(06)
register
10
Preset multiple
(16)
4X registers
17
Read/Write 4X
(23)
registers
Note: In the Modbus data message, register 4xxxx is addressed as xxxx -1. For
example, register 40002 is addressed as 0001.
Access Information
R
0304 FB STS WORD
the DCU profile 32-bit Status word.
Supported only by the DCU profile, ie, when
CTRL PROFILE
Additional information
device.
Presets a value into a single register (4X reference). When
broadcast, the function presets the same register reference in all
attached slaves.
Presets values into a sequence of registers (4X references). When
broadcast, the function presets the same register references in all
attached slaves.
Performs a combination of one read operation and one write
operation (function codes 03 and 10) in a single Modbus
transaction. Write operation is performed before the read
operation.
2, ie, the most significant word of
setting is
DCU
PROFILE.
5305 EFB
1607