342 Fieldbus control with fieldbus adapter
After the module configuration parameters in groups
FBA DATA IN
and
(shown in section

Drive control parameters

adjusted when necessary.
The new settings will take effect when the drive is next powered up, or when
parameter
5127 FBA PAR REFRESH
Drive control parameters
After the fieldbus communication has been set up, the drive control parameters listed
in the table below should be checked and adjusted where necessary.
The Setting for fieldbus control column gives the value to use when the fieldbus
interface is the desired source or destination for that particular signal. The
Function/Information column gives a description of the parameter.
Parameter
CONTROL COMMAND SOURCE SELECTION
1001 EXT1
COMMANDS
1002 EXT2
COMMANDS
1003
DIRECTION
1010 JOGGING SEL COMM
1102 EXT1/EXT2
SEL
1103 REF1 SELECT
1106 REF2 SELECT
OUTPUT SIGNAL SOURCE SELECTION
1401 RELAY
OUTPUT 1
55 FBA DATA OUT
Setting for
fieldbus control
COMM
COMM
FORWARD
REVERSE
REQUEST
COMM
COMM
COMM+AI1
COMM*AI1
COMM
COMM+AI1
COMM*AI1
COMM
COMM(-1)
51 EXT COMM
have been set, the drive control parameters
on page 342) must be checked and
is activated.
Function/Information
Selects the fieldbus as the source for the start
and stop commands when EXT1 is selected as
the active control location.
Selects the fieldbus as the source for the start
and stop commands when EXT2 is selected as
the active control location.
Enables the rotation direction control as defined
by parameters
1001
control is explained in section
handling
on page 323.
Enables jogging 1 or 2 activation through the
fieldbus.
Enables EXT1/EXT2 selection through the
fieldbus.
Fieldbus reference REF1 is used when EXT1 is
selected as the active control location. See
section
Reference selection and correction
page 346.
Fieldbus reference REF2 is used when EXT2 is
selected as the active control location. See
section
Reference selection and correction
page 346.
Enables relay output RO control by signal
COMM RO
WORD.
MODULE,
and 1002. The direction
Reference
54
on
on
0134