294 Actual signals and parameters
All parameters
No.
Name/Value
8402 SEQ PROG
START
DI1(INV)
DI2(INV)
DI3(INV)
DI4(INV)
DI5(INV)
NOT SEL
DI1
DI2
DI3
DI4
DI5
DRIVE START Sequence programming activation at drive start
TIMED FUNC 1 Sequence programming is activated by timed function 1.
TIMED FUNC 2 See selection
TIMED FUNC 3 See selection
TIMED FUNC 4 See selection
RUNNING
Description
Selects the source for the Sequence programming
activation signal.
When Sequence programming is activated, the
programming starts from the previously used state.
If Sequence programming activation signal is lost, the
Sequence programming is stopped and all timers and
outputs (RO/TO/AO) are set to zero. Sequence
programming state
(0168 SEQ PROG
unchanged.
If start from the first Sequence programming state is
required, the Sequence programming must be reset by
parameter
8404 SEQ PROG
Sequence programming state is always required, reset and
start signal sources
(8404
must be through the same digital input.
Note: The drive will not start if no Run enable signal is
received
(1601 RUN
Sequence programming activation through inverted digital
input DI1. 0 = active, 1 = inactive.
See selection DI1(INV).
See selection DI1(INV).
See selection DI1(INV).
See selection DI1(INV).
No Sequence programming activation signal
Sequence programming activation through digital input DI1.
1 = active, 0 = inactive.
See selection DI1.
See selection DI1.
See selection DI1.
See selection DI1.
See parameter group
TIMED FUNC
TIMED FUNC
TIMED FUNC
Sequence programming is always active.
STATE) remains
RESET. If start from the first
and
8402 SEQ PROG
ENABLE).
36 TIMED
FUNCTIONS.
1.
1.
1.
Def/FbEq
NOT SEL
START)
-1
-2
-3
-4
-5
0
1
2
3
4
5
6
7
8
9
10
11